CATEGORIES

Rly3

The SICK safety relay having safety sensors with potential free outputs. It is mainly used for discrepancy monitoring and cross circuit detection.

Specification

Features
Applications Evaluation unit
Compatible sensor types Safety sensors with potential-free outputs
Safety-related parameters
Safety integrity level SIL3 (IEC 61508)
SILCL3 (IEC 62061)
Category Category 4 (ISO 13849-1)
Performance level PL e (ISO 13849-1)
PFHD (mean probability of a dangerous failure per hour) 1.0 x 10-9
TM (mission time) 20 years (ISO 13849-1)
Safe state in the event of a fault The N/O is open; in other words, the safety-related enabling current paths are interrupted.
Stop category 0 (IEC 60204-1)
Functions
Sensor monitoring Discrepancy monitoring
Cross-circuit detection
Restart interlock
Reset Automatic
Manual
External device monitoring (EDM)
Interfaces
Connection type Front connector with spring terminals
Inputs 2 safety inputs
1 input for reset pushbutton or external device monitoring (EDM)
Outputs 2 enabling current paths (safe)
2 application diagnostic outputs (not safe)
3 test pulse outputs (not safe)
Display elements LEDs
Configuration method Hard wired
Electrical data – Operating data
Voltage supply PELV or SELV
Supply voltage VS 24 V DC (16.8 V … 30 V)
Residual ripple ≤ 2.4 V
Power consumption ≤ 2.5 W (DC)
Electrical data – Safety inputs
Number 2
Input voltage
HIGH 24 V DC (11 V … 30 V)
LOW 0 V DC (–3 V … 5 V)
Input current 4 mA … 6 mA
Activation time tolerance between the two start buttons ≤ 3 s
Electrical data – Reset pushbutton or external device monitoring (EDM) input
Number 1
Input voltage
HIGH 24 V DC (11 V … 30 V)
LOW 0 V DC (–3 V … 5 V)
Input current 4 mA … 6 mA
Electrical data – Enabling current paths
Response time 10 ms
Number 2
Type of output N/O contacts, positively guided
Contact material Silver alloy, gold flashed
Switching voltage 10 V AC … 230 V AC
10 V DC … 230 V DC
Switching current 10 mA … 6 A
Total current 12:00 AM
Mechanical life 1 x 107 switching cycles
Overvoltage category III (EN 60664-1)
Rated impulse withstand voltage Uimp 6 kV (EN 60664-1)
Electrical data – Application diagnostic outputs
Number 2
Type of output Push-pull semiconductor output, short-circuit protected
Output voltage
HIGH ≥ Vs – 3 V
LOW ≤ 3 V
Input current (NPN) ≤ 15 mA
Output current (PNP) ≤ 120 mA
Electrical data – Test pulse outputs
Number 3
Type of output PNP semiconductors, short-circuit protected
Output voltage ≥ Vs – 3 V
Test pulse width 2 ms
Test pulse interval 40 ms
Mechanical data
Dimensions (W x H x D) 18 mm x 124.6 mm x 85.5 mm
Weight 130 g
Ambient data
Enclosure rating IP20 (IEC 60529)
Ambient operating temperature –25 °C … +55 °C
Storage temperature –25 °C … +70 °C
Air humidity 10 % … 95 %, Non-condensing
Interference emission According to IEC 61000-6-4
Interference resistance According to IEC 61326-3-1
According to IEC 61000-6-2
According to IEC 60947-5-1
Classifications
ECl@ss 5.0 27371990
ECl@ss 5.1.4 27371990
ECl@ss 6.0 27371819
ECl@ss 6.2 27371819
ECl@ss 7.0 27371819
ECl@ss 8.0 27371819
ECl@ss 8.1 27371819
ECl@ss 9.0 27371819
ECl@ss 10.0 27371819
ECl@ss 11.0 27371819
ETIM 5.0 EC001449
ETIM 6.0 EC001449
ETIM 7.0 EC001449
ETIM 8.0 EC001449
UNSPSC 16.0901 41113704